PowerSig
MULTIFUNCTION
TRANSDUCER
M560-AT*
OPERATING MANUAL
M560AT~1.PM5 01/08/101, 12:511
Przeglądanie stron 0
1 2 3 4 5 6 ... 62 63

Podsumowanie treści

Strona 1 - OPERATING MANUAL

PowerSigMULTIFUNCTIONTRANSDUCERM560-AT*OPERATING MANUALM560AT~1.PM5 01/08/101, 12:511

Strona 2 - CONTENTS

2.6 Changing Baud Rate.ACTION : Click Baud RateBox.COMMENTS :Chose Baud Rate. Either2400, 4800, 9600, 19200.2.7 Changing Parity.ACTION : Click Parity

Strona 3

Note if wording in Modbus box is "NO REPLY FROMNODE". Check polarity connection of RS485 link at M560and PC. Check that M560 has auxiliary p

Strona 4

10ACTION : Click onbutton.COMMENTS : This buttonmoves forward oneparameter, and displays thisparameter in the sixth boxe.g. PF Avg is now shown.ACTI

Strona 5

112.10 Stopping and pausing communication.2.10.1 To pause communication.ACTION : Click on Pausebutton.COMMENTS : Thecommunication pauses.ACTION : Cli

Strona 6

122.11 Starting timer.The timer is real time clock provided by the Monitorprogram. It is useful for checking Watt hour readings etc.ACTION : Click St

Strona 7

132.12.1 Entering General Pass CodeACTION : Click GeneralPass Code ButtonCOMMENTS :Enter value box isdisplayed.2.12 Security code. (General Pass Code)

Strona 8

142.13.2 To Unlock M560 communications settings.ACTION : Click UnlockButton.COMMENTS :M560 communication port isnow unlocked.ACTION : Click LockButton

Strona 9

2.14 Programming of nominal voltage and current inputsand ratios.The program allows the user to program the nominalvoltage and current inputs and rati

Strona 10

ACTION : Enter valueCOMMENTS : Enter11000 (11kV). Click onO.K.2.14.2Changing CT ratio.For example to change for 200/5A change to 400/5 :-ACTION : Clic

Strona 11

172.15 Pulsed Output (Pulsed output is an option. If the unitdoes not have this option please proceed to section 2.16)The M560 measures and displays

Strona 12

CONTENTSUpdate: M560 Version 41. INTRODUCTION2. PROGRAMMING PARAMETERS3. PROGRAMMING ANALOGUE OUTPUTS4. PROGRAMMING MODBUS REGISTERSEQUENCE.5. RS485

Strona 13

182.15.2 Selecting Relay output pulse width.The pulse width can be set between 0msec (off) and200msec, in steps of 20msec.ACTION : Click On PulseWidth

Strona 14

19ACTION : NoneCOMMENTS : Divisor setfor 1. This means after every1 unit that M560 counts therelay pulses once.ACTION : Select Divisorrequired.COMMENT

Strona 15

202.16.1 Programming demand periods.Example to change from 8 min to 30 min demand period :ACTION : Click OnDemand Button.COMMENTS : "EnterValue&q

Strona 16

2.17 Resetting of demand period.The Demand reset programming mode allows the User toreset the demand period to zero. i.e Wd (Average WattDemand Impor

Strona 17

22ACTION : Click OnRegisters BoxCOMMENTS : The order ofthe displayed measurementsnow matches that of theModbus registers in thenode. See section 32.20

Strona 18

23ACTION : Enter NodeAddress Required.COMMENTS : Example ifnode address 30 is requiredenter 30 and click OK Button2.21 Calibration Factors.This option

Strona 19

242.21.2 Reading Calibration DataACTION : Manually recordcalibration figures for V1,V2, V3, I1, I2, I3.COMMENTS : Thesevalues must be stored withthe

Strona 20

2.25 Additional Information that M560 Monitor95provides :25Model = Model No 560Version = Software versionnumberType = System Type.either 3ph 4W (3 pha

Strona 21

26Stack Free = Nodes internalprogram, stack state.Parity Errors = number oferrors since node coldstarted.CRC errors = Number ofCRC errors since node c

Strona 22

27The parameters are set by default to following readings. Allcan be changed if required, see section 2.3 to 2.6. Responsetime = 300mS, Node = 1, Bau

Strona 23

M560 Version 4 update:RS485 response time decreased to better than 10ms.Choice of four Endian settings for floating point transmission.Modbus 3X Regis

Strona 24

3.3 Opening communication port.ACTION : Click CommsButton.COMMENTS :Choose which P.C.communication port 1 or 2.Click on Com 1 or Com 23.4 Addressing P

Strona 25

3.5 Selecting Parameters For Analogue Outputs.ACTION : Click onAvailable Outputs BoxCOMMENTS :Using the up and downcursor on your PC you canscroll thr

Strona 26

ACTION : Click onAvailable Outputs Box.COMMENTS :Using the up and downcursor choose parameterrequired for analogueoutput 2. Example if Wattsin Phase 3

Strona 27

ACTION : Click on >>Button.COMMENTS :Output 3 = Hz. (Thisappears in Node No 1 Box)3.6 Selecting Output Values & Ranges For AnalogueOutputs.T

Strona 28

ACTION : Click On ZeroOffset Box CH2.COMMENTS :Nominal Box is set at 100%= 20mA . Zero offset box isset at 0 = 0mA.ACTION : Enter Value 50Into Nominal

Strona 29

ACTION : Click On ZeroOffset Box CH3.COMMENTS :Nominal Box is set at 100%= 20mA . Zero offset box isset at 0 = 0mA.ACTION : Enter Value 5Into Nominal

Strona 30

ACTION : Click Read ButtonCOMMENTS :Reads all parameterinformation andcorresponding outputs.34M560AT~1.PM5 01/08/101, 12:5234

Strona 31

4.0 PROGRAMMING MODBUS REGISTERS SEQUENCEIf the unit has not been provided with a communicationoption this section is not relevant, please move to sec

Strona 32

Baud Rate = 9600, Parity = None364.4 Opening communication port.ACTION : Click on CommsButton.COMMENTS :Choose which communica-tion port, 1 or 2. Clic

Strona 33

For Example if the order required is Total Watt (W sum),System Frequency (Hz), Average Power Factor of System(PF Avg) and Maximum VA Demand (Max VAd)

Strona 34

M560 V4 Modbus 4X registersModbus Register Name Mode40001 (0x0000) SYSTEM VOLTAGE (R/W)40003 (0x0002) SYSTEM CURRENT (R/W)4000

Strona 35

ACTION : Click >> Button.COMMENTS :Hz (This appears in NodeNo. Box)ACTION : Click SendButton.COMMENTS :All information in the NodeNo. box is s

Strona 36

Note. The parameters not selected are placed in the defaultorder after the parameters chosen.4.6 Additional Options the Modbus Register Tool ProgramOf

Strona 37

405.1 M560 Modbus Protocol5.0 RS485 COMMUNICATIONThe RS 485 allows remote reading and programming of theM560 via a host computer. The communicationpro

Strona 38

5.1.2 Communication FormatBaud rate : 2400, 4800, 9600, 19200Low level character format :With Odd or Even parity = 1 start bit, 8 data bits, 1 parity

Strona 39

CRC CalculationsTo calculate the Cyclic Redundancy Check value.Load a word register with 0xFFFF (CRCREG)Repeat the following for each character in the

Strona 40

435.3.6 Timing5.3.7 Response time.Modbus response time from reception of the last characterto the transmission of the 1st character in its reply is le

Strona 41

44An EXCEPTION error will be generated if the node cannotfulfil the task set by the Master or the Slave receives invaliddata in its data slot.Exceptio

Strona 42

A sample write packet will look like this:-[Node][04][start address][No. of Double RegistersRequested][CRC(2 bytes)]e.g. To read line to neutral volta

Strona 43

Continued :-Modbus Add. Register Add. Register Name Order No.30033 (0x20) W 1 1730035 (0x22) W 2 1830037 (0x24) W 3 1930039 (0x26) VAr 1 2030041

Strona 44

Modbus Register Order: Overview (also see section 4 andhelp file of M560 software)M560 has the facility to reorder its Modbus 3X registers tosuit an e

Strona 45

31.1 GeneralPowerSig M560 multifunction transducer is a completemeasuring system in a single 100mm Din rail mount case.Measuring Phase Volts, Phase C

Strona 46

ExampleTo obtain all 3 line powers in a 4 wire system on Node 23hPacket from master :A sample write packet will look like this:-[Node][1E][start addr

Strona 47

ReadPacket from master format :[Node addr][03][Register start addr.(2 bytes)][No of reg(2bytes)][CRC (2 bytes)]Response form Slave format :[Node addr

Strona 48

[Node][10][start address][No. of Double Registers][Datalength in bytes][CRC(2 bytes)]e.g. To set Node 23h System Voltage and System Currenttogether:-[

Strona 49

40049 (0x30) I/P V2 GAIN FACTOR (R/W)40051 (0x32) I/P V3 GAIN FACTOR (R/W)40053 (0x34) I/P I1 GAIN FACTOR (R/W)40055 (0x36) I

Strona 50

Response from slave format ;[23][03][08][8 bytes of data(2 regs x 4 bytes)] [CRC (2 bytes)]To set both System Volts and System Amps on Node 23hPacket

Strona 51

533) The number of parity errors detected by the node.(counts up to 255 then flips over to zero)4) The number of framing errors detected by thenode.(c

Strona 52

6. INSTALLATION6.1 CaseThe M560 is designed for snap on to Din rail mount 35 x7.5mm. Complies with DIN-EN 50022CASE DIMENSIONS5410035 70DIN-EN 50022/

Strona 53

6.2 Auxiliary SupplyThe auxiliary supply can be connected in parallel with themeasuring input voltage, but this restricts the measuringrange of the in

Strona 54

6.5 Voltage TransformersConnection of voltages higher than the rated voltage, thatis specified on the M560 data label, is possible usingexternal volta

Strona 55

7. CONNECTION DIAGRAMS7.1 All connections must be made ensuring, all starts andfinishes of current and voltage transformers are connectedas shown.SING

Strona 56

Export Reactive Energy (VAr.h), Power Factor per phase(P.F.), System Power Factor (P.F.), Amp Demand, WattDemand, V A Demand, Maximum Amp Demand,Maxim

Strona 57

3 PHASE 3 WIRE UNBALANCED LOAD583 PHASE 4 WIRE UNBALANCED LOADM560AT~1.PM5 01/08/101, 12:5258

Strona 58

8. M560 SPECIFICATIONSINPUTRated Un Direct connected voltages between 57.8and 600V. Specify nominal.Range 2-120% UnBurden 0.5VA per phaseOverload 1.

Strona 59

AC voltage 115 or 230 or 277volts (±15%)DC voltage 12 / 24 / 48 / 110 / 125 voltsAUXILIARY60RELAY OUTPUT : (optional)Pulsed output W.h or VAr.h or VA.

Strona 60

61APPROVALSUL. C-UL, CSA PendingENCLOSUREFixing Snap on to Din rail35 x 7.5mm complies withDIN-EN 50022Mounting Any positionEnclosure Code Case IP 50

Strona 61 - EN61326-2

1.4 Communications (optional)The M560 has the option of providing RS485 output of allmeasured parameters.The serial port option enables remote reading

Strona 62

62.0 PROGRAMMINGIf the unit has not been provided with a communicationoption this section is not relevant, please move to section 6installation.2.1 Us

Strona 63

ACTION : Click ResponseTime Box.COMMENTS :Enter Value of responsetime. Minimum value300mSec.2.4 Changing Node NumberACTION : Click Node No.Box.COMMENT

Komentarze do niniejszej Instrukcji